Control parameters: the reference

The authoritative UK Legionella numbers in one place, each with its source and a plain-English note. The figures the whole site, and your scheme of control, point back to.

Checked against HSE ACoP L8, HSG274 and the BS standards on 27 June 2026.See what changed ›

Last reviewed 27 June 2026Machine-readable JSON

Indicative guidance only. Every value here must be confirmed against the current edition of the cited document and applied through a competent, site-specific risk assessment. Figures are common UK baselines, not a substitute for professional judgement or the source standard.

Temperature control

ParameterValueWhere it appliesSource & notes
Hot water storage temperature≥ 60 °CStored in the calorifier / hot water cylinderStore hot water hot enough that the whole vessel stays at temperature. Confirm the figure and any healthcare variation against current guidance and your risk assessment.HSE HSG274 Part 2 (2024), “Operation and inspection of hot and cold water systems”, p.70See: Hot water temperature guidelines to prevent Legionella, Calorifier maintenance for Legionella: inspection, drain-off and sludge removal
Hot water at the outlet≥ 50 °C ( ≥ 55 °C healthcare ) within ~1 minSentinel hot outlets, time to reach temperatureDistributed hot water should reach the listed temperature quickly at the tap; healthcare uses the higher figure. Balance against scald risk via TMVs.HSE HSG274 Part 2 (2024), “Operation and inspection…”, p.70; healthcare 55 °C per HTM 04-01See: Hot water temperature guidelines to prevent Legionella, TMV maintenance: balancing scald risk and Legionella control
Cold water at the outletbelow 20 °C within ~2 minSentinel cold outlets, after runningKeep cold water cold. Warming of cold mains in summer or near heat sources is a common failure; confirm the target against your risk assessment.HSE HSG274 Part 2 (2024), “Operation and inspection of hot and cold water systems”, p.70See: Cold water temperature guidelines to prevent Legionella
Legionella growth range20–45 °CWater temperature where the bacterium multipliesDormant below ~20 °C, multiplies fastest 20–45 °C, killed progressively above ~50 °C and rapidly above ~60 °C. Indicative ranges.HSE HSG274 Part 2 (2024), Introduction; WHO (2011) “Water safety in buildings”See: Pipe Scale, Corrosion and Biofilm: How Surface Condition Drives Legionella Risk, Temperature control basics for Legionella prevention
Time to kill at temperature~60 °C: minutes · ~50 °C: hoursHow quickly heat inactivates LegionellaHigher temperatures kill faster. Used as the basis for thermal disinfection; confirm dwell times against current guidance.HSE HSG274 Part 2 (2024), Introduction; WHO (2011)See: Thermal disinfection: using heat to control Legionella

Microbiology & action levels

ParameterValueWhere it appliesSource & notes
Legionella result: in control≤ 100 CFU/LHot & cold water systems (HSG274 Part 2)System generally considered under control; continue routine monitoring. Indicative band: interpret with your risk assessment and a UKAS lab.HSE HSG274 Part 2 (2024), “Microbiological monitoring” (para 2.123), p.86See: Understanding lab results: CFU counts and what they mean, Legionella sampling 101: how and why to test your water
Legionella result: review> 100 to 1,000 CFU/LHot & cold water systems (HSG274 Part 2)Review control measures and resample; if the majority of samples are positive, act. Indicative band.HSE HSG274 Part 2 (2024), “Microbiological monitoring” (para 2.123), p.86See: What to do if you get a positive Legionella test, Understanding lab results: CFU counts and what they mean
Legionella result: immediate action> 1,000 CFU/LHot & cold water systems (HSG274 Part 2)Investigate, review controls and consider disinfection. Indicative band; your risk assessment and a competent person guide the response.HSE HSG274 Part 2 (2024), “Microbiological monitoring” (para 2.123), p.86See: What to do if you get a positive Legionella test
Cooling tower action levels≤ 100 · > 100–1,000 · > 1,000 CFU/LCooling towers & evaporative condensers (HSG274 Part 1)Per HSG274 Part 1 Table 1.11: not detected/up to 100; >100 and up to 1,000 (low-level, reassess); >1,000 (act). Interpreted alongside the tower’s biocide and aerobic/dip-slide regime (Table 1.10).HSE HSG274 Part 1 (2024), Table 1.11 “Comments and action levels in response to legionella analysis results”, p.47See: Cooling towers and evaporative condensers: high-risk systems

Monitoring frequency

ParameterValueWhere it appliesSource & notes
Sentinel outlet temperaturesMonthlyNearest & furthest hot and cold outletsSentinels bracket each service at its extremes. Frequency is risk-assessment led; monthly is the common baseline.HSE HSG274 Part 2 (2024), “Operation and inspection of hot and cold water systems”, p.70See: Sentinel outlets: what they are and how to monitor them, Routine monitoring and flushing: the basics
Representative outlet temperaturesOn rotation (all over a set period)A representative selection of other outletsRotate so a representative spread of outlets is checked over the period set by your risk assessment (often a year).HSE HSG274 Part 2 (2024), “Operation and inspection of hot and cold water systems”, p.70See: Routine monitoring and flushing: the basics
Calorifier flow & return temperatureMonthlyHot water storage vesselRecord both flow and return; a low return can indicate stratification or scale.HSE HSG274 Part 2 (2024), “Operation and inspection of hot and cold water systems”, p.70See: Calorifier maintenance for Legionella: inspection, drain-off and sludge removal
Flushing little-used outletsWeekly (or as risk-assessed)Outlets not used regularlyRun little-used outlets to replace stagnant water; weekly is the common baseline, set yours by risk assessment.HSE HSG274 Part 2 (2024), “Operation and inspection of hot and cold water systems”, p.70See: How to implement a flushing programme for Legionella control, Water Age Explained: Why Residence Time Drives Legionella Risk

Inspection & maintenance

ParameterValueWhere it appliesSource & notes
Cold water storage tank inspectionAnnually (typical)CWST condition, lid, screens, sedimentInspect condition and cleanliness; clean/disinfect if needed. Interval is risk-assessment led.HSE HSG274 Part 2 (2024), “Operation and inspection of hot and cold water systems”, p.70See: Water tank inspections: checking for Legionella risk
Calorifier inspection / drain-offAnnually (typical)Internal inspection and/or drain to check for sludgeCheck for sludge/scale at the base; frequency depends on findings and risk assessment.HSE HSG274 Part 2 (2024), “Operation and inspection of hot and cold water systems”, p.70See: Calorifier maintenance for Legionella: inspection, drain-off and sludge removal
TMV service & fail-safe testPer manufacturer (commonly 6–12 monthly)Thermostatic mixing valvesService, descale and fail-safe test; healthcare (HTM 04-01) and manufacturer schedules may be more frequent.HSE HSG274 Part 2 (2024), “Operation and inspection…”, p.70; plus TMV manufacturer instructionsSee: TMV maintenance: balancing scald risk and Legionella control
Showerhead clean & descaleQuarterly (typical)Showerheads and hosesDismantle, clean and descale; more often where scaling is heavy. Risk-assessment led.HSE HSG274 Part 2 (2024), “Operation and inspection of hot and cold water systems”, p.70See: Showerhead cleaning and descaling schedules
Risk assessment reviewNo fixed expiry: review on triggersThe Legionella risk assessment itselfReview regularly and whenever the system, its use, or the people exposed change. The "every two years" figure is a common prompt, not a legal expiry.HSE ACoP L8 (2013), “Carrying out a risk assessment”, p.12; BS 8580-1:2019, clause 10 (risk review and reassessment)See: Reviewing and updating your Legionella risk assessment regularly

Disinfection

ParameterValueWhere it appliesSource & notes
Shock chlorination50 mg/L for ≥ 1 h, with ≥ 30 mg/L free residual at the endChemical disinfection of a water systemHSG274 para 2.135: dose to 50 mg/L (ppm) for a minimum 1 hour contact, with at least 30 mg/L free residual chlorine remaining at the end; lower concentrations over longer contact times are acceptable per BS 8558. High-hazard work under COSHH; confirm against current guidance.HSE HSG274 Part 2 (2024), “Cleaning and disinfection” (para 2.135), p.88; lower concentrations / longer contact times per BS 8558See: How to shock-chlorinate (disinfect) a water system: a step-by-step procedure
Thermal disinfection (pasteurisation)≥ 60 °C at every outlet, defined dwellHeat disinfection of a hot water systemRaise temperature and run each outlet for the defined period; manage scald risk. Confirm temperature/dwell against current guidance.HSE HSG274 Part 2 (2024), “Cleaning and disinfection”, p.87See: Thermal disinfection: using heat to control Legionella
ParameterValueWhere it appliesSource & notes

Need these as a printable card? Each row also feeds our record templates and calculators. For the documents behind the numbers, see standards & guidance.